Contact No : +91 - 77080 20128

Flooded Tubular Plate,Premium-STANTUBULAR

FEATURES

  • Tubular Technology
  • High Acid Volume per AH
  • Deep Cycle Design
  • Common Side Venting
  • Resistance to Abuse
  • Electrolyte level indicator
  • Tower type Design
  • Conforms to IS 13369 - 1992
ADVANTAGES

  • Very Long Life
  • User Friendly
  • Acid volume per AH is 30% more than ordinary Tubular Battery, acts as a Coolant and ensures Very Low Maintenance
  • SEnsures Consistent Quality
  • Suited for use in areas of Frequent Power-cuts (800 to 1000 cycles of Deep Discharge as against 300/400 cycles of other Batteries)
  • Can withstand Overcharge Better
  • Occupies Less Floor Space, totally new Look
  • Less Polluting, Environment Friendly
APPLICATION

  • Home UPS & Inverters

SPECIFICATIONS CHART
Battery
Type
Nominal
Volts
Rated Capacity (Ah) at 27C (1.280 sp.gr.) Dimensions (mm) ± 3 mm Weight ± 5 ‰
(Kg)
20 Hr @
1.75V/Cell
10 Hr @
1.75V/Cell
5 Hr @
1.75V/Cell
3 Hr @
1.75V/Cell
1 Hr @
1.75V/Cell
Length Width Height* Dry Filled
ST500 12 150 120 100 86 60 500 187 430 31.00 56.80
ST550 12 165 135 112 97 68 500 187 430 35.33 57.50
ST650 12 200 160 133 115 88 500 187 430 45.00 72.60
*the height mentioned is up to terminal top.

BATTERY CHARGING SCHEDULE
Battery
Type
Nominal
Volts
Rated Capacity (Ah) at 27C 20hr @ 1.75V / Cell Initial Charge at Constant Current (A) Minimum Ah Input During Initial Charge Approx. Acid Qty (1.220 Sp. Gr.) in ltrs/Cell Constant Potential Limiting Current (A) Trickle Charge Current (mA)
Start (upto 2.36 vpc) Finish (upto 2.75 vpc) Min Max
ST500 12 150 14.4 7.2 540 23.80 30 120 480
ST500 12 165 16.0 8.0 610 20.00 34 135 540
ST650 12 200 19.2 9.6 720 21.60 40 160 640
Initial Charging Instructions
  • Filling in specific gravity 1.2200.005 at 27C
  • Rest period 12 hrs.
  • Minimum Ah input as per above chart.
  • In order to reduce the charging time, the initial charging current would be as specified till 2.36 Volts/Cell followed by finishing current as specified till 2.75 Volts/Cell.
  • However in both cases, Minimum Ah input to be given. Under no circumstances, battery temperature should exceed 50C
  • In case the temperature exceeds 50C, adequate rest to be given till the electrolyte temperature comes to ambient temp. and charging to be continued
  • Condition of fully charged
    • 3 consecutive hourly readings of specific gravity and voltage become constant
    • Top of charge voltage will be around 16.2V 16.5V
    • All cells should gas freely.
    • Minimum Ah has been given
  • Specific gravity at fully charged condition 1.2500.005 at 27C
Normal Recharging Instructions
Battery should be re-charged through an Inverter at constant potential mode of 14.4V with limited current as specified. After battery potential reaches 14.4V, the battery should continue in float charge mode at constant potential of 13.8V.


Home | About Us | Services | Inverters | Batteries | Online UPS | Solar | Security Systems | Contact Us | Enquiry | Sitemap
www.sevenhillssystems.com - All Rights ReservedDesigned by varinfotech